Precision-digital PD6000 User Manual Page 68

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 67
Model PD6000 Analog Input Process Meter Instruction Manual
68
Display Parameter Action/Setting
O-rang
Overrange
Program mA output for display overrange
u-rang
Underrange
Program mA output for display underrange
mAx
Maximum
Program maximum mA output allowed
min
Minimum
Program minimum mA output allowed
Calib
Calibrate
Calibrate 4-20 mA output (internal refer-
ence source used for scaling the output)
4 mA
4 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
20 mA
20 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
user
User I/O
Assign function keys and digital I/O
F1
F1 function key
Assign F1 function key
F2
F2 function key
Assign F2 function key
F3
F3 function key
Assign F3 function key
dI I
Digital input 1
Assign digital input 1 – 8, if expansion
modules are connected
dO 1
Digital output 1
Assign digital output 1 – 8, if expansion
modules are connected
ICal
Internal source
calibration
Enter internal source calibration (used for
scaling the meter without a signal source)
C CAL
Current
calibration
Calibrate 4-20 mA current input (internal
reference source used for scaling the input)
C lo
Current low
Calibrate low current input (e.g. 4 mA)
C Hi
Current high
Calibrate high current input (e.g. 20 mA)
v CAL
Voltage
calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input (e.g. 0 V)
v Hi
Voltage high
Calibrate high voltage input (e.g. 10 V)
Copy
Copy
Enter copy function
send
Send
Send meter settings to another meter
done
Done
Copy function completed
Diag
Diagnostics
Display parameter settings