PRECISION DIGITAL CORPORATION
89 October Hill Road • Holliston MA 01746 USA
Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
PD6200 Analog Input Rate/Totalizer
Instruction Manual
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, 10 V Inputs
NEMA 4X, IP65 Front
Universal 85-265 VAC, or 12/24 VDC Input Power Models
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Dual-Scale for Level Applications – Single Input
Isolated 24 VDC @ 200 mA Transmitter Power Supply
Signal Input Conditioning for Flow & Round Horizontal Tanks
Programmable Displays & Function Keys
Rate Displayed as Units per Second, Minute, Hour, or Day
Total, Grand Total or Non-Resettable Grand Total
9-Digit Totalizer with Total Overflow Feature
32-Point Linearization, Square Root, or Programmable Exponent
Multi-Pump Alternation Control
2 or 4 Relays + Isolated 4-20 mA Output for Rate or Total
External 4-Relays & Digital I/O Expansion Modules
USB, RS-232 & RS-422/485 Serial Communication Options
Modbus
®
RTU Communication Protocol Standard
Tare Function
Free MeterView
®
Pro Software
Page view 0
1 2 3 4 5 6 ... 107 108

Summary of Contents

Page 1 - Instruction Manual

PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com PD6200 Analog Inp

Page 2 - Registered Trademarks

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 10 DECIMAL POINT Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, o

Page 3 - Table of Contents

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 100 Display Parameter Action/Setting Description mA 4-20 mA Set meter for 4-20 mA input

Page 4

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 101 Display Parameter Action/Setting Description reset Reset To access the Reset menu rh

Page 5

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 102 Display Parameter Action/Setting Description T CF Total conversion factor Program to

Page 6 - INTRODUCTION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 103 Figure 21:1/8 DIN Panel Cutout Template

Page 7 - ORDERING INFORMATION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 104

Page 8 - SPECIFICATIONS

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 105 NOTES

Page 9 - Process Input

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 106 NOTES

Page 10 - Rate/Totalizer

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 107 NOTES

Page 11

Model PD6200 Analog Input Rate/Totalizer Instruction Manual LIM6200_H SFT039 Ver 2.200 & up 06/11 How to Contact Precision Digital  Fo

Page 12

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 11 PROGRAMMA-BLE DELAY ON RELEASE 0.1 and 999.9 seconds; applied to the first relay assi

Page 13 - RTU Serial Communications

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 12 TIME DELAY 0 to 999.9 seconds, on & off relay time delays Programmable and indepe

Page 14 - COMPLIANCE INFORMATION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 13 Modbus® RTU Serial Communications SLAVE ID 1 – 247 (Meter address) BAUD RATE 300 - 19,

Page 15 - SAFETY INFORMATION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 14 COMPLIANCE INFORMATION Safety UL & c-UL LISTED USA & Canada UL 508 Industrial

Page 16 - INSTALLATION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 15 Note: Testing was conducted on PD6200 meters installed through the cov-ers of grounde

Page 17 - Mounting Dimensions

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 16 INSTALLATION There is no need to remove the meter from its case to complete the instal

Page 18 - MAIN BOARD

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 17 Mounting Dimensions 1.76"(45 mm)0.59"(15 mm)4.77"(121 mm)2.45"(62

Page 19 - Connections

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 18 Configuration for 12 or 24 VDC Power Option Warning! Do not exceed voltage rating of

Page 20 - Power Connections

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 19 Transmitter Supply Voltage Selection (P+, P-) All meters, including models equipped wi

Page 21 - Signal Connections

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 2 Disclaimer The information contained in this document is subject to change without not

Page 22 - Relay Connections

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 20 Connectors Labeling The connectors’ label, affixed to the meter, shows the location of

Page 23 - Switching Inductive Loads

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 21 Signal Connections Signal connections are made to a five-terminal connector labeled S

Page 24 - 4-20 mA Output Connections

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 22 -++VoltageSignalmA+P-21354P+ V+COMINPUT SIGNALmA+P-21354P+ V+COMINPUT SIGNAL3-Wire Vol

Page 25 - RLY5 RLY6 RLY7 RLY8

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 23 Switching Inductive Loads The use of suppressors (snubbers) is strongly recommended wh

Page 26 - 5 VDC GND

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 24 4-20 mA Output Connections Connections for the 4-20 mA transmitter output are made to

Page 27 - SETUP AND PROGRAMMING

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 25 External Relay & Digital I/O Connections The relay and the digital I/O expansion m

Page 28 - Description LED Status

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 26 123456+5 I1 I2 I3 I4 O178O2 O3910O4 GDI 1-4 DO 1-45 VDC GND Figure 17: Digital I/O Mo

Page 29

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 27 SETUP AND PROGRAMMING The meter is factory calibrated prior to shipment to read in mil

Page 30

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 28 Front Panel Buttons and Status LED Indicators Button Symbol Description LED Status

Page 31

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 29 Display Functions and Messages The meter displays various functions and messages durin

Page 32

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 3 Table of Contents INTRODUCTION -------------------------------------------------------

Page 33 - Main Menu

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 30 Display Parameter Action/Setting Description value (up to 32 points) Dis 2 Display 2

Page 34 - Increment Digit

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 31 Display Parameter Action/Setting Description RLY 2 Relay 2 Relays 2-8 setup Note: Rela

Page 35

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 32 Display Parameter Action/Setting Description GT rst Grand total reset Program grand to

Page 36

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 33 Main Menu The main menu consists of the most commonly used functions: Reset, Control,

Page 37

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 34 Setting Numeric Values The numeric values are set using the Right and Up arrow buttons

Page 38

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 35 Setting Up the Rate/Totalizer Meter (setup) The Setup menu is used to select: 1. Inpu

Page 39

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 36 Setting the Input Signal (input) Enter the Input menu to set up the meter to display c

Page 40

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 37 Dual-Scale for Level Application The analog input can be displayed in two different sc

Page 41 - 10 VDC

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 38 Setting the Decimal Point (dEc pt) The decimal point may be set with up to five decima

Page 42

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 39 prog sCale Prog Cal Prog t CF Prog t tb Prog Grand Total Settings t rst Prog Additio

Page 43 - The display

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 4 Reset Menu (reset) ------------------------------------------------------------ 34Cont

Page 44

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 40 SCALE Prog Inp 1 SCALe 04.000 Inp 1 Inp 2 SCALe 20.000 Inp 2 dis 1 SCALe 004.000 dis

Page 45 - Display Setup Menu

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 41 Error Message (Error) An error message indicates that the calibration or scaling proce

Page 46

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 42 Time Base, Total Conversion Factor & Total Reset The time base, total conversion f

Page 47

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 43 Calibrating the Meter with External Source (Cal) To scale the meter without a signal s

Page 48 - Relay Assignment (Assign)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 44 Setting the Display Parameter & Intensity (dsplay) The main display (Big) can be p

Page 49 - Setting the Relay Action

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 45 Display Setup Menu After setting up the input and the display, press the Menu button

Page 50 - Programming Time Delay

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 46 Character Set for Engineering Units Display (d unit) The small display can be programm

Page 51

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 47 Setting the Relay Operation (relay) This menu is used to set up the operation of the r

Page 52 - Automatic (non-latching)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 48 Assign relay rly 1 relay delay relay dly 1 delay on dly 1 set 1 rly 1Note: The set

Page 53

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 49 Setting the Relay Action Operation of the relays is programmed in the Action menu. The

Page 54

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 5 Acknowledging Relays ------------------------------------------------------ 62Pump Alt

Page 55

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 50 Programming Set and Reset Points High alarm indication: program set point above reset

Page 56

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 51 Relay and Alarm Operation Diagrams The following graphs illustrate the operation of th

Page 57

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 52 Low Alarm Operation (Set < Reset) ResetSetInputRelayLEDenergizedde-energizedonoffRe

Page 58 - Time Delay Operation

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 53 High Alarm with Fail-Safe Operation (Set > Reset) RelayLEDInputAutomatic (non-latch

Page 59 - Relay Operation Details

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 54 Low Alarm with Fail-Safe Operation (Set < Reset) ResetSetInputRelayLEDAutomatic (no

Page 60 - Front Panel LEDs

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 55 Pump Alternation Control Operation Pump 1Relay1 SetRelay2 ResetRelay2 SetRelay1

Page 61 - Latching Relay (LatcH)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 56 Rate Relay Sampling Operation SetResetRelayLEDInputSampleTimeSampleTimeSampleTime When

Page 62 - PDA1044 Digital I/O Module

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 57 Signal Loss or Loop Break Relay Operation The following graph shows the loop break op

Page 63 - Pump Alternation Operation

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 58 Time Delay Operation The following graphs show the operation of the time delay functi

Page 64

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 59 Relay Operation Details Overview The relay capabilities of the meter expand its useful

Page 65

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 6 Table of Figures Figure 1: 1/8 DIN Panel Cutout and Mounting ...

Page 66

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 60 Front Panel LEDs The LEDs on the front panel provide status indication for the followi

Page 67 - Setting Numer

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 61 Non-Latching Relay (Auto) Automatic reset only Condition LED RelayNormal Off Off Alarm

Page 68 - Setting Numeric

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 62 Latching Relay (Lt-Clr) Manual reset only after alarm condition has cleared Condition

Page 69

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 63 Pump Alternation Control Applications (Altern) For pump control applications where two

Page 70 - Password

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 64 Application #2: Pump Alternation Using Relays 3 & 4 1. Relays 1 and 2 are set up f

Page 71 - Advanced Features Menu

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 65  If the backup pump is not able to keep up, and the level reaches 7000 gallons, re

Page 72

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 66 Setting Up the Interlock Relay (Force On) Feature Relays 1-4 can be set up as interloc

Page 73

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 67 Scaling the 4-20 mA Analog Output (Aout) The 4-20 mA analog output can be scaled to pr

Page 74

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 68 Setting Up the Password (pass) The Password menu is used for programming three levels

Page 75 - Noise Filter Bypass (bypass)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 69 Total Reset Password & Non-Resettable Total The total and the grand total can be p

Page 76

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 7 ORDERING INFORMATION Standard Models 85-265 VAC Model 12/24 VDC Model Options Installed

Page 77 - Select Menu (SElEct)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 70 Making Changes to a Password Protected Meter If the meter is password protected, the m

Page 78 - Number of

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 71 Advanced Features Menu To simplify the setup process, functions not needed for most ap

Page 79

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 72 Advanced Features Menu & Display Messages The following table shows the functions

Page 80 - Low-Flow Cutoff (CutofF)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 73 Display Parameter Action/Setting O-rang Overrange Program mA output for display overr

Page 81

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 74 Display Parameter Action/Setting done Done Copy function completed Diag Diagnostics D

Page 82 - Tare (tare)

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 75 Noise Filter (filter) The noise filter is available for unusually noisy signals that c

Page 83

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 76 Modbus RTU Serial Communications (serial) The meter is equipped with serial communicat

Page 84

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 77 Select Menu (SElEct) The Select menu is used to select the signal input conditioner ap

Page 85 - PDA1200 Meter Copy Cable

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 78 Square Root Linearization (Square) The square root function can be used to linearize t

Page 86 - Display flashes

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 79 Round Horizontal Tank Linearization (rHt) This function automatically calculates the v

Page 87 - METER OPERATION

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 8 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. Gener

Page 88 - Maximum/Minimum Readings

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 80 Low-Flow Cutoff (CutofF) The low-flow cutoff feature allows the meter to be programmed

Page 89 - TROUBLESHOOTING

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 81 Programmable Function Keys User Menu (user) The User menu allows the user to assign th

Page 90 - reset diaG

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 82 Tare (tare) The tare function zero’s out the display. In the case of scale weight, tar

Page 91

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 83 2. Press the Up arrow button to scroll to the Internal calibration menu (ICAL) and pr

Page 92

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 84 Tips:  Low and high input signals can be any valid values within the range of the me

Page 93

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 85 Meter Copy Function (Copy) The Copy function is used to copy (or clone) all the settin

Page 94

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 86 Meter Copy or Cloning Instructions ! Caution! Do not connect the two meters to the sam

Page 95 - Troubleshooting Tips

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 87 METER OPERATION The meter is capable of accepting current (0-20 mA, 4-20 mA) and vol-t

Page 96

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 88 Maximum/Minimum Readings The max & min readings (peak & valley) reached by the

Page 97

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 89 TROUBLESHOOTING The rugged design and the user-friendly interface of the meter should

Page 98

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 9 NORMAL MODE REJECTION Greater than 60 dB at 50/60 Hz ISOLATION 4 kV input/output-to-pow

Page 99

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 90 Reset Meter to Factory Defaults When the parameters have been changed in a way that i

Page 100

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 91 Factory Defaults & User Settings The following table shows the factory setting for

Page 101

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 92 Parameter Display Default Setting User Setting Total reset T rst Manual Grand tota

Page 102

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 93 Parameter Display Default Setting User Setting Fail-safe relay 4 Fls 4 Off On delay

Page 103

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 94 Parameter Display Default Setting User Setting Slave ID (Address) Slave Id 247 Baud

Page 104

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 95 Troubleshooting Tips Symptom Check/Action No display at all Check power at power conne

Page 105

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 96 Alphabetical List of Display Functions & Messages Display Parameter Action/Setti

Page 106

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 97 Display Parameter Action/Setting Description bypASs Bypass Set filter bypass value C

Page 107

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 98 Display Parameter Action/Setting Description d-Inty Display intensity Set display in

Page 108 - SFT039 Ver 2.200 & up

Model PD6200 Analog Input Rate/Totalizer Instruction Manual 99 Display Parameter Action/Setting Description GT tb Grand total time base Program gran