Precision-digital PD6000 User Manual Page 70

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 69
Model PD6000 Analog Input Process Meter Instruction Manual
70
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a stan-
dard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an
RS-232 or RS-422/485 adapter option is required; see
Ordering Infor-
mation
on page 7 for details.
Warning!
Do not connect any equipment other than Precision
Digital’s expansion modules, cables, or meters to the
RJ45 M-LINK connector. Otherwise damage will occur to
the equipment and the meter.
Note: More detailed instructions are provided with each optional serial
communications adapter.
Note: Refer to the PD6000/PD7000 Modbus Register Tables located at
www.predig.com for details.
baud
Serial
SlavId
Serial
tr dly
Serial
serial
t-byt
Serial
Parity
Serial
When using more than one meter in a multi-drop mode, each meter
must be provided with its own unique address. The meter address
(Slave ID) may be programmed between 1 and 247. The transmit delay
may be set between 0 and 199 ms. The parity can be set to even, odd,
or none with 1 or 2 stop bits.
The PD6000 can also be connected to another PD6000 with a special
PDA1200 cable, allowing the user to copy all the settings from one me-
ter to another, using the
Copy function.
Page view 69
1 2 ... 65 66 67 68 69 70 71 72 73 74 75 ... 95 96

Comments to this Manuals

No comments