Setting Up the Interlock Relay Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the
interlock feature:
1. Access the
SetupRelayAction menu and set the action to off.
Act 1
rly 1
Off
Act 1
setup
relay
setup
rly 1
relay
2. In the Advanced features –
User menu program any of the digital
inputs to
Force On any of the internal relays (1-4).
user
F1
user
F On 1
dI 1
dI 1
user
3. Connect a switch or dry contact between the +5V terminal and the
corresponding digital input (dI-1 to dI-4) terminal.
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND
SW2
SW1
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off)
when SW1 & SW2 switches (above) are closed. If the contacts to these
digital inputs are opened, the corresponding front panel LEDs flash indi-
cating this condition. The processes being controlled by the interlock
relay will stop, and will re-start only after the interlock relay is re-
activated by the digital inputs (switches).