PD6870 Loop-Powered Process Meter Instruction Manual
8
Electromagnetic Compatibility
EN 61326:2006
Safety requirements for measurement, control, and
laboratory use – Industrial
Group 1 Class A ISM emissions requirements
EN 61326:2006
Safety requirements for measurement, control, and
laboratory use
RFI – Amplitude
Modulated
80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)
±2 kV DC mains, ±1 kV other
3 V, 0.15-80 MHz, 1 kHz 80% AM
SAFETY INFORMATION
Read complete instructions prior to installation and operation of the meter.
Installation and service should be performed only by trained service
personnel. Service requiring replacement of internal components must be
performed at the factory.
Disconnect from supply before opening enclosure. Keep cover tight while
circuits are alive. Conduit seals must be installed within 18" (450mm) of
the enclosure.
Verify that the operating atmosphere of the meter is consistent with the
appropriate hazardous locations certifications.
If the meter is installed in a high voltage environment and a fault or
installation error occurs, high voltage may be present on any lead