PD865 Snooper Modbus
Serial Input Meter Instruction Manual: Register Table
69
SLAVE MODE REGISTER TABLE
40001 – 40008: Process Value (PV), Max PV, Min PV, relay status, reset max & min Display value, Alarm & Relay status,
Relay acknowledge.
40009 – 40027: Initialize meter, Lock, Mode, Data Type, Display Decimal point, Linear/Square Root/Exponent, Exponent
value, Serial settings, Unit address, byte-to-byte timeout, Number of scaling points, Slave Response
timeout, Poll Time, Brightness, Bypass, Cutoff, Filter, Float decimal point.
40101 – 40128: Relays; Set & Reset points, Operating Mode, Turn-on & Turn-off delays.
40301 – 40317: 4-20mA output; Mode, Over-range value, Under-range value, Maximum allowed, Minimum allowed,
Communications Break value, Display Value 1, Display Value 2, Output 1, Output 2, Data (mA/bits), and
gain & offset calibration factors.
40401 – 40464: Input and Display values for 2 – 16 point scaling.
49101 – 49116: Product ID, Firmware Version, and Manufacturing Serial Number.
49201 – 49215: Reserved for user data.
Register
1
Name Access
Limits
or
Range
2
Data
Type
3
Function
Code(s)
Comments
Number
Address
(hex)
40001 –
40002
0 – 1
(0000–
0001)
Display
value
Read
Write
-199999 to
+999999
Long 03, 04, 16
Represents the display value without the decimal point. Decimal
point setting in 40013.
40003 –
40004
2 – 3
(0002–
0003)
Maximum
Display
value
Read
Write
-199999 to
+999999
Long 03, 04, 16
Represents the Maximum display value, excluding the decimal
point, since last power up or Max. Value reset. Decimal point
setting in 40013. Writing any value will reset the max to the
present display value.