Display Parameter Action/Setting
nmin
Min Analog
Output
Enter the minimum value allowed for the
Analog Output.
CALib
Calibration
Enter the Analog Output Calibration menu.
nman
Manual
Perform a manual calibration on the Analog
Output.
Auto
Automatic
Perform an automated calibration on the
Analog Output.
d-inty
Display Intensity
Set the display intensity.
info
Information
Display software version and S/N
information.
Display Math Function (func)
The input data can be scaled using one of three selectable functions:
Linear, Square Root, or Programmable Exponent.
funC
linear square Prog e
No pts
Enter Exponent
Enter Number
of Points
Linear: The Linear function can be programmed to have from 2 to
16 points.
The Square Root and Programmable Exponent functions have 2
points.
The Programmable Exponent can be programmed from 0.50000 to
2.99999. Setting it to 0.50000 is the same as selecting the Square
Root function.