PD663 Loop-Powered Meter Instruction Manual
18
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press the
Right arrow to select next digit and the Up arrow to increment digit. The two left-
most digits on the display are set as a single digit, able to display -19 to 29.
The digit being changed blinks.
Press the Enter button, at any time, to accept a setting or Menu button to exit
without saving changes.
The decimal point is set using the Right or Up arrow button in the Setup-decimal
point menu.
Programming the Meter
It is very important to read the following information, before proceeding to
program the meter:
There is no need to recalibrate the meter for milliamps when first received from
the factory.
The meter is factory calibrated for milliamps prior to shipment. The calibration
equipment is certified to NIST standards.
Use the Scale (SCL) menu to enter scale parameters without applying a live
signal.
Alternatively, use the Calibrate (CAL) menu to apply a signal from a calibrator or a
4-20 mA transmitter to calibrate the meter.
Inputs may be calibrated or scaled to any display within the range of the meter.
Additional parameters, not needed for most applications, are viewed and
programmed with the Advanced features menu, see Advanced Features Menu,
page 24.